4. Continued
5. The heater
blows black
smoke out of
the vent stack.
• Gas valve
Air damper setting
• Dirt on burner blower wheel
• Improper flue pipe setup or flue pipe
restrictions
• Gas manifold pressure
• Incorrect burner orifice size
• Restricted heat exchanger
• If there is power at the flame safeguard control and no power out to the
solenoid valve, replace the flame safeguard control. Check for continuity
between the terminals on the solenoid valve coil.
• Rough setting at 4.5. Minor adjustments from the rough settings can be made
to achieve a smooth sounding burner with no soot from the flue pipe.
• Clean the burner blower wheel with a small brush.
• Refer to the flue pipe chart in this manual. Check flue for restriction.
• Use a low pressure gauge (0-15 inches of water column) with 1/8” NPT inlet.
Install gauge in the pressure tap port located on the output side of the gas
valve. Run the heater. Adjust the pressure by turning the pressure adjusting
screw (located on the input side top of the gas valve) counter clockwise until
the gauge reads 3” W.C.(Propane) & 3.2” W.C.(Nat Gas). Refer to pipe sizing
charts in the Heat Wagon Engineering Guide. Heater requires 9-14” W.C. inlet
pressure.
• For propane, use size .201.
For natural gas, use size .261.
• Remove flue pipe and use a flashlight to inspect the inside of the heat
exchanger. The access panel is located in the front panel which is welded to
the flue pipe.
VG175 TR
OUBLESHOOTING
Symptom P
ossible Causes Possible Solutions